Just took a brief poll in the office to talk about the 5psf horizontal loading required by the code for wood stud design on walls per [IBC 1607.13]. Interesting...
The commentray for the IBC 2003 talks about the loading being related to pressurization, or nominal impact loads. The transient nature of these loads seems to indicate the use of the Cd=1.6 factor.
The poll reveals that most of us are using a Cd = 1.6 for our combinations involving wind and seismic as applies to the Fb bending criteria. For the D+L load case, we are NOT applying the 5psf or 1.6 factor.
Steve points out that the 1997 UBC [1611.5] is actually a LOT more clear about the 5psf: It specifically mentions that the 5psf need not be applied simultaneously with the wind or seismic loads, and further gives deflection criteria...
Steve and I speculate that the 5spf may be used in lieu of actual horizontal seimic loads on wall (unless there is a heavy "special case" phenomenon) , and wind should be applied as per standard wind calcs. The question is whether to apply the 5psf as a live load to the D+L load case. When you "factor" (excuse the pun here) in the 97 UBC, it seems that we should consider the 5psf in this case as well (what Cd to use though?)
So to summarize:
The commentray for the IBC 2003 talks about the loading being related to pressurization, or nominal impact loads. The transient nature of these loads seems to indicate the use of the Cd=1.6 factor.
The poll reveals that most of us are using a Cd = 1.6 for our combinations involving wind and seismic as applies to the Fb bending criteria. For the D+L load case, we are NOT applying the 5psf or 1.6 factor.
Steve points out that the 1997 UBC [1611.5] is actually a LOT more clear about the 5psf: It specifically mentions that the 5psf need not be applied simultaneously with the wind or seismic loads, and further gives deflection criteria...
Steve and I speculate that the 5spf may be used in lieu of actual horizontal seimic loads on wall (unless there is a heavy "special case" phenomenon) , and wind should be applied as per standard wind calcs. The question is whether to apply the 5psf as a live load to the D+L load case. When you "factor" (excuse the pun here) in the 97 UBC, it seems that we should consider the 5psf in this case as well (what Cd to use though?)
So to summarize:
- With the Seismic combination - we are generally using 5spf in lieu of hor seismic loads, with Cd = 1.6 (for flexure and axial)
- With wind combinations - the wind does not generally apply with the wind loads to a 2x4 wall (the main point of concern)
- With dead and live combos - we have NOT been applying the 5psf - but should. On this note, we're floating out the idea that we may apply a Cd =1.6 for flexural component of the design only. Cd for other aspects will remain at 1.0.